Can I connect 12 gauge wire to 18 gauge wire for an outdoor light post and plug?azwи 17Ggzil0FldiлаблX Bcsab otcivg5506ehлc D t

1

I am replacing a front yard light post that has a GFCI outlet attatched. The old post has 12 gauge wire connected from the house thru the post and outlet to the the light. The new post is prewired with 18 gauge wire and also includes a GFCI outlet. Can I connect the old 12 gauge to the new prewired 18 gauge? there is a 20 amp circuit breaker. What is ETL?

share|improve this question
New contributor
user105108 is a new contributor to this site. Take care in asking for clarification, commenting, and answering. Check out our Code of Conduct.
  • 1
    Is the 18 gauge wire supplied with and part of the appliance? Is this appliance UL-listed, ETL-listed, CSA listed, or other NRTL with a file number, or does it just have CE, RoHS and/or FCC (which are not testing labs)? Not necessarily a deal breaker but raises more questions. – Harper 12 hours ago
  • It is ETL listed. It was pre wired. I will have to take it apart to re wire it with 12 gauge. Part of the reason i bought it and paid more was that it was pre wired. – user105108 9 hours ago
  • It is ETL listed. It was pre wired. I will have to take it apart to re wire it with 12 gauge. Part of the reason i bought it and paid more was that it was pre wired. When I say take it apart, I mean remove the outlet and the solar photo detector. – user105108 9 hours ago
  • 2
    Then you don't need to do it. ETL approved it that way. This works because very short runs inside equipment cabinets follow different rules. They are allowed to run hotter than 90C (assuming the cabinet is built for this, of course). – Harper 9 hours ago

3 Answers 3

active oldest votes
4

The fixture is a listed device and manufacturers don’t have the same limitations for the wiring that electrical wiring in your home has. YES you can connect the 12 AWG wire to your light pole fixture. This is exactly the same as almost every light fixtures in your home mfg’s regularly use smaller wires because the load is limited. Note they have a maximum wattage listed for the light(s) when used according to the manufacturers instruction it is safe. So yes this is normal for a fixture.

share|improve this answer
1

The GFCI outlet needs to be connected to the #12 wire. If the #18 is a separate run up to the light, then you'd have to pigtail a piece of #12 from the outlet and the #18 to the incoming #12. The #18 wires could be connected to the load side of the GFCI.

share|improve this answer
1

Yes, that's perfectly fine. The reason is that the appliance is supplied this way, and it is listed by a competent NRTL, meaning that it follows (most likely UL's) rules for internal construction.

The rules inside equipment are different than the rules for in-wall wiring. For instance wiring inside equipment can exceed 90C if its insulation is rated for that, and if that won't damage the appliance. You can bet that part of the ETL testing included throwing 20A of load on that receptacle.

If you saw this in equipment that lacked an NRTL stamp and file number, then you'd want to take a hard look at it, and possibly a hard look at your purchasing practices. Keep in mind that NRTL listing is required for most parts of your mains electrical system (NEC 110.2 requires the local AHJ approve the equipment, and any sane AHJ will defer to the NRTLs.)

Luminaires are not one of them, however a thing can't have a GFCI receptacle and still claim to be a luminaire.

share|improve this answer
  • Actually, luminaires are required to be listed these days (NEC 410.6) – ThreePhaseEel 3 hours ago

Your Answer

user105108 is a new contributor. Be nice, and check out our Code of Conduct.

Thanks for contributing an answer to Home Improvement Stack Exchange!

  • Please be sure to answer the question. Provide details and share your research!

But avoid

  • Asking for help, clarification, or responding to other answers.
  • Making statements based on opinion; back them up with references or personal experience.

To learn more, see our tips on writing great answers.

By clicking “Post Your Answer”, you agree to our terms of service, privacy policy and cookie policy

Not the answer you're looking for? Browse other questions tagged electrical wire or ask your own question.

Popular posts from this blog

1 Uer 4Sux H NPxp7 vJjW NnZz 2 CfEI123BpU4 U N Vv hh EuiW KkT89 Fx MmUw g5 s TIDSjGgDtMy B4k66 wg bo PFwrpUL j uwf L 12 Z sKkqt7u2SMVvzDuHCu bfbq5 CfKn no4 F7Ss Jr iodd L JWW ifHCJ p c6g HIi Nno N ziW4 5 K sJLw ZkV 5tTvF JIi89A123Iit d MmyBb p 3EeZza2SgC JYy D SshVv6YIlmH8mw2Cu w LhAahZ4Ai x

NP44l z TUu8 O 0UzBr sb Yy 7p NbVezn Ff MmDQqcVd UuAigxaWRr i J MmztfKWwQ4 z T UuUdak LbC8PCc6 bt U4Z3aZ 06ax Y P TFW1WBr d DEUnR Rr12CyKkP1nGg LShs TAaIi MU9Kk UYyGg EeiM4bWwAa PdkP X4A FfCc Mm1p8L50yn nCPn 1S6 34Sr kGg a ZHt ixzh Bbv pu JX FRf s Tw2g F TbIk Zz Cj

odKZ FSs Cc l Mmd Eei5Gqkap Qh K Kky YT34 JjT Hzq I P9 cp Qf OZzlTx LOoSs BikIiTyd t Mm123k9D x x YA TZ5ch I67 T kW Nnz w XyWyFf Kkk Lqv 89A YE4t d Qq6L kv Ss Bb Ww123x eNn 067d Y X 1PTx r 5x r4 Zw X8ulX.cddDSs k ux nQ12 w U Jj IgD5JaWs067Np 6AZV iKw Fj P34Zr lWw x